Features
IEX-2 module, analog light controller 4 analog outputs 0..10V 3 analog/digital inputs 2 digital inputs light, motion and IR sensor input
Technical specifications
Input type | dry contact, internal pull-up 12V 2mA |
analog input 0..10V (10 bit, 0..1023) | |
potentiometer 0..10k (10 bit, 0..1023) | |
Sensor input | RHKF-U (light), IR-580-IQ (motion), |
LRI8134 (multisensor) |
Analog output | 0..10V (8 bit, 0..255) |
Output current | 10mA per channel, sink or source |
Number of ballasts | 50 per channel, 100 total |
Light sensor | |
Power supply output | 12V 25mA |
Input range | 0..10V (10 bit, 0..1023) |
Internal pull-up | none |
Motion detector | |
Power supply output | 12V 25mA |
Signal type | dry contact |
Internal pull-up | 12V 1mA |
Infrared receiver | |
Power supply output | 5V 10mA |
Signal type | TTL level, active low |
Internal pull-up | 5V 0.5mA |
Power supply | 24V (18..28V), 150mA |
Galvanic isolation | none (ballasts must be SELV) |
Operating conditions | 0..45°C, 0..95% rh non-condensing |
Dimensions | 108x86x46mm |
Weight | 200g |
Degree of protection | IP42 |
Standards | EN 60730-1 |
Order Code
LC-S |