programmable controller
8 digital inputs
4 relay outputs 8A
4 NPN outputs 1A
2 Wiegand interface
1 RS232/485, 1 RS232
Ethernet, USB, IEX-2
EnOcean gateway (optional)
230V AC power supply
Technical specifications
Input type (ix00..ix07) | dry contact, internal pull-up 12V 2mA |
Galvanic isolation | none |
Cable length | 50m |
Output type (qx12..qx15) | NPN transistor 30V 1A |
Permanent load | 1.5A qx12+qx13 and 1.5A qx14+qx15 |
Protection | short circuit, overvoltage, overheating |
Galvanic isolation | none |
COM1 interface | RS232 (RJ9), RS485 (terminals) |
Galvanic isolation | none (RS232), none or 1kV (RS485) |
Cable length | 10m (RS232), 50 or 500m (RS485) |
Transmit/receive | automatic switching (RS485) |
Wiegand input | active low, internal pull-up 3V3 1mA |
Pulse timing | 20us min width, 20ms max spacing |
Power output | 12V 500mA (RFID reader) |
Power supply | 100..240VAC, 50/60Hz |
Power consumption | 1W (no load), 10W max. |
IEX-2 power output | 24V 250mA (IEX-2 modules) |
Total power output | 6W (IEX-2+Wiegand) |
Standards | EN 60730-1 |
Other specifications are the same as Cybro-3.
Order code
Cybro-3W-230 | 230V AC |
Cybro-3W-230-OC | 230V AC, opto-isolated RS485 |
Cybro-3W-230-ENO | 230V AC, EnOcean gateway |
Cybro-3W-230-OC-ENO | 230V AC, EnOcean, opto-isolated RS485 |