Features

IEX-2 module 12 RTD inputs

Features

IEX-2 module 12 RTD inputs

Technical specifications
Input type Pt100/1000 (DIN751) auto selectable, measuring range -100..300°C
Ni100/1000 (DIN43760) auto selectable, measuring range -50..160°C
Ni100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°C
potentiometer 0..2000ohm
Sensor current 190uA (each sensor)
Wire resistance 20ohm max. (3-wire mode)
Resolution 14 bits in 0.1% mode
12 bits in 0.5% and 1% mode
Temperature drift +/-0.01%/°C of measuring range
Calibration reference 150.00ohm, 1500.0ohm
Input mode
Power supply 24V (18..28V), 50mA
Galvanic isolation 1kV beetwen digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensing
Mounting DIN rail (35mm)
Dimensions 53x107x58mm
Weight 160g
Degree of protection IP20
Level of ambient pollution 2
Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Order Code
AiR-12